Control stations
The control station CS-PH/5/A is designed for remote control, asynchronous electromotor protection against overcurrent” and short circuit”, with a short-circuited rotor” (from 1 to5 pcs.) and outgoing connections” in mine three-phase electrical networks” with the insulated transformer neutral”.The type of climatic version is Ó5 according to State standard 15150-69, State Standard 15543.1-89”.
The station provides:
- protection against short-circuit currents of outgoing power circuits” and circuits supplied by the integrated transformer”;
- protection against outgoing power circuit overcurrent;
- protection against inadmissible thermal overload of pluggable equipment”;
- protection against opening” and short circuit” in remote control circuits”;
- protection against automatic switching in case of supply voltage rise up to 150% from the rated voltage”;
- protection against ground circuit opening or resistance rise of outgoing circuits exceeding permissible level;
- the locking device preventing tap switching in case of outgoing circuits fault condition and phase-to-ground insulation drop below the permissible level;
- protection against current leak in power circuits (input and output), circuits supplied by “127 V secondary side of the integrated transformer” and in 220 V internal supply circuits”;· remote control of every power circuit;
- alarm system for normal and emergency state protection and locking devices;
- zero protection.
Basic parameters and specifications
Parameter | Standard |
Rated voltage of insulation and three-phase alternate current power circuit supply with (50±1) Hz frequency, V | 1140; 1000; 660 |
Number and capacity of electromotors supplied and controlled by the station”, pcs., W | 2*380 3*100 |
Light transformer capacity, kWA | 8 |
Rated voltage of light transformer secondary side, V | 127 |
Maximum dimensions, mm | 3000*1160*900 |
Maximum weight, kg | 1200 |
Operational mode: continuous short-time short-time repetitional | S1 S2 S3 |
Ambient air temperature, °Ñ | from — 5 to +35 |
Relative ambient humidity at the temperature (25±2) °Ñ, % | 98±2 |
Operational position in space | vertical |
Maximum altitude above sea level, m | 1000 |
Maximum depth below sea level, m | 1500 |
Version according to State Standard24754-81 and State Standard 30852.0-2002 | ÐÍ2 — ExibIU |
Level of remote-control intrinsically safe electrical circuit according to State Standard 30852.10-2002 | ib |
Minimum ingress protection rating | IP54 |
Minimum average error-free running time, h | 1000 |
Maximum recovery time, h | 1 |
Minimum average operating life, years | 8 |
Example of order record
"Control station CS-PH/5/À ÒÓ BY 600175052.011-2005"